Ring Main Unit The best solution for Power Distribution Systems Contents 4 특장점 6 구성 10 네트웍원격제어 12 정격및종류 14 LBS 15 차단기

Similar documents
XGT InfoU_K_160411

iP5A_K 내지( )

Print

Starvert iG5A_K3_101224

경제성과안정성이높은차단기 / VCB IEC 신규격개정에따른한전의교류차단기표준규격 (ES150) 의개정및적용 (2004 년 10 월 ) 으로인해한전수화력발전소용으로개발된제품으로, 차단성능향상및안전성과신뢰성을확보한국내최초의대용량 (40~50kA) 발전소용 VCB 시리즈를완

형명및정격 (MCCB) 배선용차단기 (AB - 시리즈 ) 프레임의크기 50AF Type 형명 정격 극수 (Pole) 정격전류 (In) A 정격전압 (Ue) AC (V) DC (V) 정격절연전압 (Ui) V 정격임펄스전압 (Uimp) kv 정격차단전류 (ka) 주1) A

Standard Drive Panel_140701

?뗡뀶?믟뀱?솽꼶?듄꼮??

REVIEW CHART

Microsoft PowerPoint (RMU).ppt

Super Solution Susol Susol Low Voltage Switchgear & Motor Control Center

InfoU_K_100713

101104_2_Starvert FP5_K

Option&단독_목차_.PDF

품질과서비스를통한고객만족 -- LS 고압진공전자접촉기 세계적으로기술력을인정받고있는자체생산의진공인터럽터를채택한 LS 고압진공전자접촉기는, 공인기관에서개발시험에합격하여품질의우수성을인정받고있습니다. 2I

101214_Starvert iG5A_K

스마트주택용분전반_160331

1. REACTOR TAP 90% 로변경, 제작공급한사유 - 고객요청사항은 REACTOR 80% 운전기준임. - 삼성테크윈에서사용하는표준 REACTOR 사양은 80%, 75%, 70% 로 STARTER 도면은표준사양으로제출됨. - 동프로젝트용모터사양서 / 성적서확인결과

熔断器

RS-8 (Modbus Protocol) 를통해상위감시제어시스템에간편하게직접연결하여 MC제어및 MC 상태, MMS상태, TOR 상태 Monitoring이가능한 Motor Starter입니다.

Starvert iG5A_K_131018

- 2 -

11 계기용 절환개폐기딩전랒계용전류계용 예 : AS, VS 12 기중차단기 13 트립코일붙이기중차단기 14 UV 배선용차단기포함. 복선도는 2극인경우를나타낸다단극, 직렬트립코일병렬, 부족전압트립코일붙이 15 직류고속도차단기 16 교류차단기 OCB, VCB, GCB 17

Total - Solution 제공으로 쾌적하고 생산적인 산업사회를 창조하는 산업용 전기ㆍ자동화 분야의 Leader LS산전의 기술로 완성한 Tri-MEC Air LBS, ASS로 향상된 제품의 성능과 기술의 차이를 느끼십시오. 2I

Turbine Digital Flowmeter SEMI U+ 특징 PVC, PTFE, P.P, PVDF 등 다양한 재질 Size, 유량, Connection별 주문제작 정밀성, 내화학성이 우수 4~20mA, Alarm, 통신(RS485) 등 출력 제품과 Controll

일진전기는세계최고수준의기술과원가경쟁력으로최고의제품과서비스를제공하는중전기분야의 Global Leader 입니다.

AVSHH100B10 IM.~20.


Vector Diagram ( 벡터도확인 ) 입력전압과전류의위상을그림으로표현한항목 DI, DO Monitoring ( 입. 출력접점감시 ) 입. 출력접점각각의현재 On/Off 상태를확인할수있어차단기조작및연동시험시정상동작이되지않을때원인분석에유용함. DI MONITORIN

2/9 목차 1. 목적 3/9 2. 적용분야 3/9 2. 제품 3/9 2. 요건 ( 표준문서목록 ) 3/9 3. 인증절차 3/9 3.1 검사용시료발췌 3/9 3.2 시료의적합성평가 3/9 3.3 결과평가와마크사용허가 4/9 4. 사후관리절차 4/9 4.1 제품의적합성평

온습도 판넬미터(JTH-05) 사양서V1.0

SF6 GAS INSULATED Pad Mounted Load Break Switch Technology SPS series Pad Mount type for underground line Rating 5.8kV 6A 5/6Hz Line up 4 Way - Automa

歯동작원리.PDF

<4D F736F F D204B4F454D FBEC6C5A95FBAB8C8A35FBDC3BDBAC5DB5F76395FC0BDBFB5C1A6B0C52E646F6378>

Leader in Electrics & Automation Upgraded for the global best worth! 배선용차단기 / 누전차단기 외부구조 및 표기사항 내부구조 및 적용기술 기종일람표 MCCB 기종일람표 ELCB 형명및정격 부속장치 형명체계 특성곡선

Microsoft Word - KSR2015A135

5. Kapitel URE neu

Prime-MEC Power Fuse

ePapyrus PDF Document

SEMI U+

À̵¿·Îº¿ÀÇ ÀÎÅͳݱâ¹Ý ¿ø°ÝÁ¦¾î½Ã ½Ã°£Áö¿¬¿¡_.hwp

Microsoft Word - PLC제어응용-2차시.doc

72129o

Susol 신화는 Susol VCB 로이어집니다! Susol Retrofit VCB 를통해노후된전력기기를안정적으로간단하게교체함으로써, 교체시간단축, 저비용, 고효율, PNL 수명연장이가능합니다. Contents 기본기능과차단동작 6 규격및인증 8 VCB 외부구조 10

BS-K1217-M□□-3012_ProductGuide_KR_PDF

SURGE PROTECTIVE DEVICE 전원 전원 전원 +E +E +N+E

100AF 125AF 250AF NType SType HType NType SType HType ABN102c ABN102 ABS102c ABH102c ABN202c ABS202c ABH202c ABN103c ABN103 ABS103c ABH103c ABN203c AB

>> Specification 전기적특성 시스템특성 입력 (DC) 출력 (AC) 형명 인증및규격 보호기능 상수 운전방식 토폴로지 최대전력 MPPT 전압범위 동작시작전압 최대전압 최대전류 입력단자수 단자당허용전류 정격전력 정격전압 정격전류 주파수 전류왜율 역률 LSTP-

ACB Air Circuit Breaker A-2

Leader in Electrics & Automation GIPAM MANAGER Electric Equipment

MR-3000A-MAN.hwp

DC Link Application DC Link capacitor can be universally used for the assembly of low inductance DC buffer circuits and DC filtering, smoothing. They

Microsoft PowerPoint 상 교류 회로

ez-shv manual

Color C60 / C70 Printer 본제작물은 Color C60/C70 Printer 로출력하였습니다.

GSH-20V 24kV Switchgear

?.,,,.. / OSHA( ) NFPA( ) ANSI/ISA( / ) TIA( ) IEC( ) CENELEC( ) IEEE( ).....?,,.. Fluke 160- FC %.,? NEC( ) 100 " / ". ( )....,,,, EMI, RFI.

개인용전기자극기의 안전성및성능평가가이드라인

2I BKS 서지보호기는교류 50/60Hz, 220V(BKS-A,C) 및 380V(BKS-E) 전원시스템에적용하며전기계통의낙뢰또는서지과전압에대해보호한다. 보호기가정상일때표시기는녹색이되고동작후 ( 비정상, 사고후 ) 표시기는적색을나타낸다.

PowerPoint Presentation

QSE-CI-AP-D.xlsx

- 2 -

7 LAMPS For use on a flat surface of a type 1 enclosure File No. E Pilot Lamp File No. E Type Classification Diagram - BULB Type Part Mate

,,,,,, (41) ( e f f e c t ), ( c u r r e n t ) ( p o t e n t i a l difference),, ( r e s i s t a n c e ) 2,,,,,,,, (41), (42) (42) ( 41) (Ohm s law),


진공차단기 VACUUM CIRCUIT BREAKER CONTENTS 12 개요 / 14 기종전개 / 16 구조 / 18 동작구조 / 부속장치 / 34 주문형식 / 36 정격및사양 / 41 인출입 / 42 설치방식 / 46 진공밸브 / 50 사용환경 / 52 외형치수 /

슬라이드 0

Molded Case Circuit Breakers 선정 선정순서 배선용차단기 (MCCB) 검토항목 고려사항 사용회로적용규격상선식, 전압, 전류, 주파수, 규격 정격일람표 정격전류결정 전선종류, SIZE, 부하종류 온도와전선과의관계 전동기회로간선용차단기선정 전등, 전열

PD-659_SM(new)

BC6HP Korean.ai

<4D F736F F F696E74202D D3420B1B3B7F9B0EDC0FCBED0B4EBC0FCB7F95FC1A4C0E7B0A95B6E65775D>

Genie Industries http//wwwgenieliftcom Copyright 00 Genie Industries 1, 00 1, Genie Genie Industri

RFID USN_K_100107

EOCR-3EZ/FEZ 디지털과전류계전기 EOCR-3EZ 패널내장형 EOCR-FEZ 패널매입형 관통형 단자형 주요특징 MCU(Micro Controller Unit) 내장 Real Time Processing / Higher Precision 과전류보호범위 : 0.5~

Microsoft Word - SRA-Series Manual.doc

MIL-C-99 Class C, R Style Connector, Receptacle, lectrical, Wall mounting YH7(MS7 Style) PLCS 전기적특성 (lectrical ata) ltitude erating Service Rating Nom

hwp

제목을 입력하십시오

KMC.xlsm

VXS-A-C1.eps

6_5상 스테핑 모터_ _OK.indd

Microsoft Word - Installation and User Manual_CMD V2.2_.doc

PLUG & SAVE ALL in ONE Series

_20010~1.PDF

BN H-00Kor_001,160

<4D F736F F F696E74202D F303720B0A1B7CEB5EEBFEB5FBCF6C1A42E BC8A3C8AF20B8F0B5E55D>

サーボモータ用高精度減速機_AFC_Aシリーズ

대경테크종합카탈로그

GDR-AB01(V1.02) 사양서.hwp

GLHPS-D

PowerPoint Template

2I

장거리 PoE 중계기 사용설명서 DA-LP1101R DA-LP1101T Powered by

단락전류계산목적 단락전류계산법 계산법의종류 임피던스법 단락전류의계산 단락전류의종류 단락전류공급원 단락전류계산에필요한임피던스 비대칭계수 단락전류계산 상단락 단락전류계산예 수변전설비 저압배전설비 맺음말

Microsoft Word - 3msz-HY 사양서- v3_1.doc

µµ≈•∏‡∆Æ1

성적서번호 : T 항목및요구사항에대한세부사항 : 제어회로장치의종류 : 수동조작스위치, 예를들면, 푸시버튼, 로터리스위치, 풋스위치등 전자석으로동작되는제어스위치, 시간 지연또는순시, 예를들면, 접촉릴레이 파일럿스위치, 예를들면, 압력스위치, 온도감지스위치

GDR-AB02(V1.00) 사양서.hwp

MMI 구성 계전기동작상태표시램프 TFT-LCD Panel TOUCH Screen USB port USB 메모리를이용한설정파일의 Upload /Download 시사용 Manager port PC MANAGER 와기기를연결할때사용 POWER LED COMM.LED Dia

Microsoft Word MetOne237Bmanual

Transcription:

www.lsis.biz 가스절연부하개폐기 SF6 Gas Insulated Ring Main Unit RMU Super Solution

Ring Main Unit The best solution for Power Distribution Systems Contents 4 특장점 6 구성 10 네트웍원격제어 12 정격및종류 14 LBS 15 차단기

RMU 24kV SF6 가스절연 Ring Main Unit LS Ring Main Units (Susol RMU) 는정격전압 24kV 이하의지중배전선로의구분, 분기및파워퓨즈 / 차단기와연동시부하사고전류차단, 고장구간분리가가능한배전용기기입니다. 변압기와조합하여구성시수배전시스템및 Compact S/S 을구현할수있습니다. 16 퓨즈조합스위치 17 부속장치 22 동작순서도 23 외형도 25 형명체계 26 품질보증

Super Solution RMU is the solution to meet your medium voltage power distribution line needs. Susol RMU 는고압배전선로에서전력을공급하고변압기를보호하기위한모든기능을조합한기기입니다. Susol RMU 는 12/17.5/24kV 배전계통상대부분에적용가능하도록다양한구성이가능합니다 4

Technology/ 기술 SF6 가스압축분사아크소호기술 파워퓨즈조합부하측사고차단기술 VI 에의한대용량부하사고차단기술 RMU 내부사고에대한내아크기술 최적의절연설계로제품소형화 Safety/ 안전 케이블통전상태에서안전하게접근및조작가능 패널앞면에표시되는회로도 (mimic diagram) 를통한동작상태표시 전자동인터록시스템 - 케이블커버완전밀폐시에만동작가능 - 부하개폐기 (LBS) 접지상태에서만 Fuse compartment 접근가능 - 케이블통전상태확인용활선상태표시기 (voltage detector) 설치 제품내부의사고발생시사용자안전을위한내아크성능확보 Durability and usefulness/ 내구및유용성 밀폐식스텐레스탱크를사용하여먼지, 작은곤충및수분과같은 주위환경의영향을받지않음 RMU 전면에서모든기기조작및케이블접속작업가능 작업자의스위치조작위치에따라자동으로작동하는 인터록시스템으로모든개폐동작시작업자안전확보 SF6 가스재충전불필요 전동조작메카니즘과 RTU 사용시원격조작가능 퓨즈조합개폐기의경우사고발생시파워퓨즈의스트라이커핀에의해메카니즘자동개방 Saving cost/ 비용절감 설치후 HRC 파워퓨즈외의별도유지보수불필요 설치및현장조작시필요한공간을최소화하여특히좁은곳에설치유리 일체형 CB Feeder 구성 (LCL), Fuse Feeder 구성 (LFL)RMU 열반형 LBS Feeder (L), CB Feeder (C), Fuse Feeder (F) LFL type LCL type 열반형 type 5

일체형 CB Feeder 구성 RMU (LCL) 단일 Chamber 내에 2 회로 LBS 와 1 회로 CB-DS 로구성된일체형 RMU L : LBS (Load Break Switch) 부하개폐및접지 (Load break and Earthing) 기능을가진 630A 이하 3-Position 부하개폐기 C : VCB (Vacuum Circuit Breaker) 변압기및선로보호를위한 21kA 차단기 Horizontal cable bushing in front ➊ 1회로접지동작부 ➋ 차단기동작부 ➌ 1회로주회로동작부 ➍ 가스압력게이지 ➎ DS 접지동작부 ➏ 제품명판 ➐ 활선상태표시부 (VD) ➑ DS 주회로동작부 ➒ 케이블함커버 ➊ ➋ ➌ ➎ ➏ ➍ ➐ ➑ ➒ 6

일체형 RMU 제품구성 제품형식 L : LBS (Load Break Switch) L : LBS (Load Break Switch) Quantity of LBS L F/C L L F/C F : Load Break Switch-Fuse combination C : Vacuum Circuit Breaker with Disconnecting switch Quantity of F/C system 표준형단선도 LCL ( 2L1C ) LFL ( 2L1F ) 일체형 Switch-Fuse Feeder 구성 RMU 단일 Chamber 내에 2 회로 LBS 와 1 회로 Switch-Fuse 로구성된일체형 RMU L : LBS (Load Break Switch) 부하개폐및접지 (Load break and Earthing) 기능을가진 630A 이하 3-Position 부하개폐기 F : Switch Fuse (Load Break Switch-Fuse combination) 변압기보호를위한 200A Switch-Fuse Combination Horizontal cable bushing in front ➊ ➋ ➌ ➍ ➎ ➊ 1회로접지동작부 ➋ 퓨즈-스위치회로주회로동작부 ➌ 1회로주회로동작부 ➍ 가스압력게이지 ➎ 활선상태표시부 (VD) ➏ ➐ ➑ ➏ 케이블함커버 ➐ 퓨즈함커버 ➑ 제품명판 7

LLLL (4L) LCL (2L1C) LLCL (3L1C) LCCL (2L2C) 열반형 RMU 제품구성 제품형식 R : Riser LFL (2L1F) R C : CB (Vacuum Circuit Breaker with Disconnecting switch) LLFL (3L1F) L C F 열반형 LBS Feeder RMU (L) L : LBS Feeder (Load Break Switch) LFFL (2L2F) 부하개폐및접지 (Load break and earthing) 기능을가진 630A이하 3-Position 부하개폐기 L : LBS (Load Break Switch) F : Fuse (Load Break Switch-Fuse combination) 1 2 C 표준형단선도 F 5 6 3 R L C F 1 가스압력게이지 2 제품명판 3 활선상태표시부 (VD) 4 케이블함커버 5 접지동작부 6 주회로동작부 7 차단기동작부 8 DS 접지동작부 9 DS 주회로동작부 10 스위치-퓨즈회로주회로동작부 11 퓨즈함커버 4 8

열반형 CB Feeder RMU (C) C : CB Feeder (Vacuum Circuit Breaker) 변압기및선로보호를위한 21kA 차단기 열반형 Switch-Fuse Feeder RMU (F) F : Switch-Fuse Feeder (Load Break Switch-Fuse combination) 변압기보호를위한 200A Switch-Fuse Combination 1 1 2 2 7 5 10 8 3 3 11 9 4 4 9

Intelligent application Susol RMU 에 RTU (Remote Terminal Unit) 를장착하고통신네트웍에연결하면 기기및선로를원격으로감시하고제어할수있게됩니다. RTU (Remote Terminal Unit) RTU (Remote Terminal Unit) 는원격지의계기와센서를통해수집한데이터를전송가능한형식으로변환하여중앙기지국의 SCADA (Supervisory Control and Data Acquisition) 시스템으로전송합니다. 또한주장치로부터제어명령을받아실시간으로수행합니다. 10

DAS/SCADA 네트웍원격제어 RTU (Remote Terminal Unit) 를 Susol RMU에장착하면 IRMU (Intelligent RMU) 가되어통신네트웍과연결이가능하며, 기기를원격으로감시하고제어할수있게됩니다. 또한사고시시스템복구뿐만아니라위치를찾아내고자동으로격리시킬수있습니다. 이렇게하면정전구간과시간을획기적으로줄이는일이가능하고높은신뢰성과뛰어난품질의전력공급을실현시킬수있습니다. System 구성 RTU 가장착된 Susol RMU 는고압네트웍을실시간으로동작하는데필요한모든기능을제공합니다. Control Center Server Dispatcher (MMI) Printer OTS DAU Hard Copier RMU with RTU RTU Small Customer Power Plant Substaion RMU with RTU Large Customer Pol Switch 11

정격및종류 정격 정격전압 kv 12 17.5 24 정격주파수 Hz 50/60 50/60 50/60 상용주파내전압 kv 28 38 50 뇌임펄스내전압 kv 75 95 125 정격전류 (busbar) A 630 630 630 정격단시간전류 (3s) ka 21 21 21 정격투입전류 ka 54.6 54.6 54.6 정격내아크전류 (1s, AFL) ka 21 21 21 정격SF6 가스압력 psi.g 5 5 5 LCL type 규격 Susol RMU 의적용국제규격 규격 IEC 62271-1 IEC 62271-100 IEC 62271-102 IEC 62271-103 IEC 62271-105 IEC 62271-200 내용 High-voltage switchgear and controlgear Part 1: Common specifications High-voltage switchgear and controlgear Part 100: Alternating-current circuit-breakers High-voltage switchgear and controlgear Part 102: Alternating current disconnectors and earthing switches High-voltage switchgear and controlgear Part 103: Switches for rated voltages above 1 kv up to and including 52 kv High-voltage switchgear and controlgear Part 105: Alternating current switch-fuse combinations High-voltage switchgear and controlgear Part 200: AC metal-enclosed switchgear and controlgear for rated voltages above 1 kv and up to and including 52 kv LFL type 사용환경 항목주위온도표고습도 조건 - 제품은아래의조건에서보관및설치되어야합니다. - 보관온도 : -40 C +60 C - 사용온도 : -25 C +40 C - 기타온도 : 문의바랍니다 - 해발 1000m 이하 - 상대습도 95% 이하 열반형 type 기타사양 항목옵션 ( 전체 ) 옵션 ( 사용자 ) 보호등급 - Manometer - VIS (Voltage Indication Systems) - 케이블커버 ( 인터록시스템부착 ) - 퓨즈커버 ( 인터록시스템부착 ) 조건 - 내부아크소호실 (21kA/1s) - 원격작동시스템 (LBS용) - 원격작동시스템 (fuse combination switch용 ) - 원격작동시스템 (CB용) - OCR (CB용) - 잠금장치 - IP 3X : 전면, IP 67 : SF6 Tank 12

형식및단선도 1. 일체형 LBS Feeder 단독구성 RMU Dimension (W H D), mm LR (1L1R) LLL (3L) LLLL (4L) LLL LR(1L1R) (3L) LLL (3L) LR(1L1R) LLL (3L) LLL (3L) LLLL (4L) LLL LLLL (3L) (4L) LLLL (4L) LLLL (4L) LLLL (4L) LLL LR(1L1R) (3L) LLL (3L) LR(1L1R) LLL (3L) 718 1186 752 1030 1186 752 1362 1186 752 LLL (3L) LLLL (4L) LLL LLLL (3L) (4L) LLLL (4L) LLLL (4L) LLLL (4L) 2. 일체형 CB Feeder 구성 RMU LC(1L1C) RC(1R1C) LC(1L1C) RC(1R1C) LC(1L1C) LC(1L1C) LCL (2L1C) LC(1L1C) LCL (2L1C) LCL (2L1C) LCL (2L1C) LLCL (3L1C) LCL LLCL (2L1C) (3L1C) LLCL (3L1C) LLCL (3L1C) LCCL (2L2C) LLCL LCCL (3L1C) (2L2C) LCCL (2L2C) LR(1L1R) RC LR(1L1R) (1R1C) LR(1L1R) LC (1L1C) LLL (3L) LLL (3L) LLL LLL (3L) LCL (3L) (2L1C) LLLL (4L) LLCL LLLL (3L1C) (4L) LLLL LLLL (4L) (4L) LCCL (2L2C) LC(1L1C) RC(1R1C) LC(1L1C) RC(1R1C) LC(1L1C) LC(1L1C) LCL (2L1C) LC(1L1C) LCL (2L1C) LCL (2L1C) LCL (2L1C) LLCL (3L1C) LCL LLCL (2L1C) (3L1C) LLCL (3L1C) LLCL (3L1C) LCCL (2L2C) LLCL LCCL (3L1C) (2L2C) LCCL (2L2C) 718 1400 752 718 1400 752 1030 1400 752 1362 1400 752 1362 1400 752 LF (1L1F) RF(1R1F) LF RC(1R1C) (1L1F) RF(1R1F) RC(1R1C) LF (1L1F) RC(1R1C) LF (1L1F) LFL LC(1L1C) (2L1F) LF (1L1F) LC(1L1C) LFL (2L1F) LC(1L1C) LFL (2L1F) LFL (2L1F) LLFL LCL (2L1C) (3L1F) LFL LCL LLFL (2L1F) (2L1C) (3L1F) LCL LCL (2L1C) LLFL (3L1F) LLFL (3L1F) LFFL LLCL (2L2F) (3L1C) LLFL LLCL LFFL (3L1F) (3L1C) (2L2F) LLCL LLCL LFFL (3L1C) (2L2F) 3. 일체형 Switch-Fuse Feeder 구성 RMU LF (1L1F) RF(1R1F) LF (1L1F) RF(1R1F) LF (1L1F) LF (1L1F) LFL (2L1F) LF (1L1F) LFL (2L1F) LFL (2L1F) LFL (2L1F) LLFL (3L1F) LFL LLFL (2L1F) (3L1F) LLFL (3L1F) LLFL (3L1F) LFFL (2L2F) LLFL LFFL (3L1F) (2L2F) RF (1R1F) LF (1L1F) LFL (2L1F) LLFL (3L1F) LFFL (2L2F) LFFL (2L2F) L R L R L L C L C C C F C F F F F RF(1R1F) RF(1R1F) RF(1R1F) LF (1L1F) LF (1L1F) LF LF (1L1F) LFL (2L1F) LFL (2L1F) LFL LFL (2L1F) LLFL (3L1F) LLFL (3L1F) LLFL LLFL (3L1F) 718 1400 752 718 1400 752 1030 1400 752 1362 1400 752 1362 1400 752 L R L R L L C L C C C F C F F F F 4. 열반형 RMU R R R R L L L L C C C C F F F F R L C F 411 1437 752 411 1437 752 521 1437 752 521 1437 752 13

Load Break Switch 정격 정격전압 kv 12 17.5 24 정격주파수 Hz 50/60 50/60 50/60 상용주파내전압 kv 28 38 50 뇌임펄스내전압 kv 75 95 125 정격전류 A 630 630 630 정격단시간전류 (3s) ka 21 21 21 정격투입전류 ka 54.6 54.6 54.6 전기적수명 E3 E3 E3 기계적수명 M1 M1 M1 접지스위치정격단시간전류 (3s) ka 21 21 21 정격투입전류 ka 54.6 54.6 54.6 전기적수명 E1 E1 E1 기계적수명 M1 M1 M1 표준사양 부하개폐및접지 (Load break and Earthing) 기능을가진 3-Position 부하개폐기 부하와접지기능용 2 개의별도축을사용하는조작기구 LBS 와 ES 용위치표시 전압표시용커패시터소겟이부착된전면의수평케이블부싱 선택사양 부하개폐기용전동조작기 보조스위치 - 부하개폐기위치 - 접지스위치위치 전압표시시스템 단락및지락표시기 3-Position 부하개폐기동작 Main close Open Earth 14

Circuit Breaker 정격 정격전압 kv 12 17.5 24 정격주파수 Hz 50/60 50/60 50/60 상용주파내전압 kv 28 38 50 뇌임펄스내전압 kv 75 95 125 정격전류 A 200/630 200/630 200/630 정격단시간전류 (3s) ka 21 21 21 정격투입전류 ka 54.6 54.6 54.6 전기적수명 E2 E2 E2 기계적수명 M1 M1 M1 단로및접지스위치정격전류 A 630 630 630 정격단시간전류 (3s) ka 21 21 21 정격투입전류 ka 54.6 54.6 54.6 전기적수명 E1 E1 E1 기계적수명 M1 M1 M1 표준사양 변압기및선로보호를위한 21kA 차단기 단로및접지 (disconnecting and earthing) 기능의 3-Position DS CB 와 DS/ES 용위치표시 전면의수평케이블부싱 CB 와 DS/ES 간인터록선택사양 CB 용전동조작기 보조스위치 - CB 위치 - 단로기위치 - 접지스위치위치 전압표시시스템 트립코일및투입코일 전류경로 대전류아크의운동방향 아크 진공인터럽터 (Vacuum Interrupter) 접점폐로 (Closing) 시회로전류는인터럽터의전극을통하여흐르고사고전류발생시또는차단이요구되는경우접점은신속하게개리됩니다. 접점표면간에발생한아크는나선형상의접점구조로인하여발생되는유도자계에의해접점주위표면을회전하여접점이국부적으로가열, 손상되는것을방지합니다. 아크를형성하는금속증기는접점주변의실드에응축하며전류영점에서아크는소멸되고금속증기발생이멈추게됩니다. 발생된금속증기생성물은급속히응축하게되어접점은절연을회복하고회복전압 ( 재기전압 ) 에견디게됩니다. 15

퓨즈조합스위치 (Switch-Fuse Combination) 정격전압 kv 12 17.5 24 정격주파수 Hz 50/60 50/60 50/60 상용주파내전압 kv 28 38 50 뇌임펄스내전압 kv 75 95 125 정격전류 A 200 200 200 전기적수명 E1 E1 E1 기계적수명 M1 M1 M1 접지스위치정격단시간전류 (1s) ka 5 5 5 정격투입전류 ka 13 13 13 전기적수명 E1 E1 E1 기계적수명 M1 M1 M1 표준사양 접지스위치가부착된 3-Position 퓨즈조합스위치 퓨즈조합스위치와접지스위치용위치표시 전면의수평케이블부싱 DIN 형퓨즈링크용퓨즈홀더 퓨즈링크정격 - 12/17.5kV : 최대 100 A, LSIS DIN 형퓨즈링크 - 24kV : 최대 75 A, LSIS DIN 형퓨즈링크 선택사양 퓨즈조합스위치용전동조작기 보조스위치 - 부하개폐기위치 - 접지스위치위치 - 퓨즈용단상태 전압표시시스템 트립코일 Cable compartment 6 3 1 7 8 9 2 5 4 1. Screened body 2. Inner screen 3. Compressing lug 4. Stress cone adapter 5. Earthing eye and lead 6. Theaded pin 7. Rear plug with test point 8. Test point 9. Conductive end cap 16

Trip Relay RMU OCR 최적의계전동작수행 과부하보호 - 51T 보호특성 (Curve 선택 ) - 51D 보호특성 ( 정한시특성 ) 지락보호 - 51ND 보호특성 ( 정한시특성 ) Remote Trip 기능 Self Power PC Manager 를통한사고이력확인 1 2 1 LED : Trip 정보및전원상태표시 3 5 7 4 6 8 Trip : Trip 상태표시 Power : 전원상태표시 2 Reset key : CPU 초기화 3 I> : 51T 전류설정, ti> : 51T 지연시간및 Lever 설정 4 Cv : 51T 동작커브설정 5 I>> : 51D 전류설정, ti>> : 51D 지연시간설정 6 In : 정격전류설정 7 Ie> : 지락전류설정, tie> : 지락지연시간설정 8 통신단자 : PC Manager 연결단자 17

Trip Relay 보호기능 51T 보호전류설정 (A) I>=In *... 0.9 0.95 1 1.05 1.1 1.15 1.2 1.3 1.4 1.5 1.6 1.8 2 2.25 2.5 NA Time delay(s) ti> a b c d e f g h i j k l m n o p ti>@(dt Curve) 0.04 0.3 0.6 1 2 3 4 6 8 10 15 30 60 120 210 300 Lever ti>@(inv Curve) 0.05 0.1 0.2 0.3 0.4 0.5 0.6 0.8 1 2 3 4 5 6 8 10 51D 보호전류설정 (A) I>> =In *... 1 2 3 4 5 6 7 8 9 10 12 14 16 18 20 NA Time delay(s) ti>>@1 * In 0.04 0.07 0.1 0.15 0.2 0.25 0.3 0.4 0.6 0.8 1 1.4 1.8 2.2 2.6 3 Accuracy ±5% 또는 Min.Trip Time(ms) 0 30 60 110 160 210 260 360 560 760 950 1330 1710 2090 2470 2850 ±40ms Max.Trip Time(ms) 40 110 140 190 240 290 340 440 640 840 1050 1470 1890 2310 2730 3150 51ND 보호전류설정 (A) IE>=In *... 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.2 1.4 1.6 1.8 2 2.5 NA Time delay(s) ti>>@1 * In 0.1 0.2 0.4 0.6 0.8 1 1.5 2 2.5 3 3.5 4 6 8 10 20 Accuracy ±5% 또는 Min.Trip Time(ms) 60 160 360 560 760 950 1425 1900 2375 2850 3325 3800 5700 7600 9500 19000 ±40ms Max.Trip Time(ms) 140 240 440 640 840 1050 1575 2100 2625 3150 3675 4200 6300 8400 10500 21000 51ND기능 ( 지락보호 ) 은 OCR이계측하는각상의 RMS 전류합이결선된 CT의 P1 P2 방향으로최소정격설정의 90% 이상에서정상동작함. Cold 상태에서인가되는각상전류 RMS 합이최소정격설정의 2배미만일경우기본오차에 ±200ms의절대오차추가적용됨. 동작특성 51T 특성 I> ti> 1.3 1.4 1.5 h 1.2 1.6 g 1.15 1.8 f 1.1 2 e 1.05 2.25 d 1.0 2.5 c 0.95 0.9 NA b timed t I> i a ti> Cv KEPCO j ANSI EI SI VI k VI l SI m LI n EI DT o VI p IEC SI I 과부하보호를위한기능으로선로고장전류에반비례하는시지연특성및정한시특성을갖습니다. 1. 기준전류설정 Knob : I> - 설정범위 : (0.9-0.95-1.0-1.05-1.1-1.15-1.2-1.3-1.4-1.5-1.6-1.8-2.0-2.25-2.5-NA)*In 2. 지연시간실정 Knob : ti> - 동작시간기준은 1*I> 일때동작시간입니다. - DT 설정범위 : 0.04-0.3-0.6-1-2-3-4-6-8-10-15-30-60-120-210-300 sec - INV 설정범위 (Lever 값 ) : 0.05-0.1-0.2-0.3-0.4-0.5-0.6-0.8-1-2-3-4-5-6-8-10 3. R/S/T 의전류중가장큰부하전류기준으로연산수행 *INV Curve 설정시동작시간 trip time = A +C T/L+DT B If - 1 Is *If : 사고전류 / Is : 설정전류 / INV 일때 DT = 0 / DT 일때 T/L = 0 18 *Curve별상수값 A B C IEC SI 0.14 0.02 0 IEC VI 13.5 1 0 IEC EI 80 2 0 IEC LI 120 1 0 ANSI SI 0.0515 0.02 0.114 ANSI VI 19.61 2 0.491 ANSI EI 28.2 2 0.1217 KEPCO SI 0.11 0.02 0.42 KEPCO VI 39.85 1.95 1.084

I>> ti>> Trip Relay 동작특성 51D 특성 t I>> ti>> 8 9 10 0.4 0.6 0.8 7 12 0.3 1.0 6 14 0.25 1.4 5 16 0.2 1.8 4 18 0.15 2.2 3 20 0.1 2.6 2 1 NA 0.07 0.04 3.0 inst 과전류보호를위한기능으로정한시특성을갖습니다. 1. 기준전류설정 Knob : I>> - 설정범위 : (1-2-3-4-5-6-7-8-9-10-12-14-16-18-20-NA)*In 2. 지연시간실정 Knob : ti>> - 설정범위 : 0.04-0.07-0.1-0.15-0.2-0.25-0.3-0.4-0.6-0.8-1-1.4-1.8-2.2-2.6-3.0 sec 3. R/S/T의전류중가장큰부하전류기준으로연산수행 I 51ND 특성 IE> tie> 0.9 1.0 1.2 2 2.5 3 0.8 1.4 1.5 3.5 0.7 1.6 1 4 0.6 1.8 0.8 6 0.5 2.0 0.6 8 0.4 2.5 0.4 10 0.3 0.2 NA 0.2 0.1 20 ground fault t IE> 지락보호를위한기능으로지락전류가설정치이상인경우시간지연후차단을수행합니다. 1. 기준전류설정 Knob : IE> - 설정범위 : (0.2-0.3-0.4-0.5-0.6-0.7-0.8-0.9-1-1.2-1.4-1.6-1.8-2-2.5-NA)*In 2. 지연시간실정 Knob : tie> - 설정범위 : 0.1-0.2-0.4-0.6-0.8-1-1.5-2-2.5-3-3.5-4-6-8-10-20 sec 3. 지락전류 = R + S + T 상입니다.( 벡터 Sum) tie> I 19

부속장치 (Option) CT (Current Transformer) 시스템최대전압 kv 0.6 1차전류 A 7.2 / 14.4 / 28.8 / 57.6 / 115.2 / 230.4 2차전류 A 0.075 정격부담 VA 0.1 정밀도 10P80 단시간전류 KA/3s 21 정격주파수 Hz 50/60 활선표시램프 (Voltage Detector) 선로케이블의활선유무를확인할수있는 LED 활선표시램프가제공되며램프의전원은부싱의정전용량성분압기로부터공급됩니다. 20

2 4 6 2 4 6 8 부속장치 (Option) Power Fuse 특징 1. LS 한류형전력퓨즈 Prime-MEC 은큰단락전류가흐를때, 퓨즈내부에서발생하는저항에의해그전류를회로고유의단락전류보다아주적은값으로제한하고최소시간내에차단하여회로를보호하므로계통기기의과전류강도를최소한으로절감할수있습니다. 2. 소형으로큰차단용량을가지고있으며, 밀폐구조이므로큐비클등설치장소가좁은곳에적합합니다. 3. 접속부 Size 를단일화함으로써기종별호환및유지보수를용이하게하였습니다. 퓨즈선정 : IEC 60787 (24kV) 기준변압기정격용량 (kva) 파워퓨즈정격전류 (A) 36 ~75 5 75 ~ 157 10 172 ~ 358 20 258 ~ 538 30 464 ~ 840 40 598 ~ 1048 50 745 ~ 1320 63 1000 ~ 1572 75 주 ) 최적의퓨즈선정은제조업체에문의바랍니다 특성곡선 1000 800 600 한류특성곡선 1000 800 600 용단특성곡선 5A 200A 400 400 10A 160A 200 200 20A 125A 한류치 ( 파고치, ka) 100 80 60 40 20 10 8 6 4 2 1 0.8 0.6 200A 160A 125A 100A 75A 63A 50A 40A 30A 20A 10A 5A 동작시간 (sec) 100 80 60 40 20 10 8 6 4 2 1 0.8 0.6 30A 40A 50A 100A 75A 63A 0.4 0.4 0.2 0.2 0.1 0.08 0.06 0.1 0.08 0.06 0.04 0.04 0.02 0.02 0.01 0.01 0.02 0.04 0.06 0.08 0.1 0.2 0.4 0.6 0.8 1 규약차단전류 ( 실효치,kA) 8 10 20 40 100 10 20 40 60 80 100 200 규약전류 ( 실효치,A) 400 600 800 1000 2000 4000 6000 8000 10000 21

부속장치 (Option) LBS/F-LBS 메카니즘용부속장치 LBS Mechanism F-LBS Mechanism ➊ ➋ ➌ ➍ ➊ LBS/F-LBS 용보조스위치 LBS/ 퓨즈조합스위치의 ON/OFF 위치를원격으로감시하기위해사용하는접점입니다. * 표준 : 각위치별 ON/OFF/EARTH ➋ 모터 (LBS 용 ) 외부전원을사용하여 LBS 의투입 / 개방스프링을차지시킵니다. 동작전압범위 : 85%~110% Vn ➌ 모터 (F-LBS 용 ) 외부전원을사용하여퓨즈조합스위치의투입스프링을차지시킵니다. 동작전압범위 : 85%~110% Vn ➍ SHT 코일 (F-LBS 용 ) 퓨즈조합스위치를외부에서개방시키는제어장치로순시 (200ms 이상 ) 로전압을공급하였을때코일이동작합니다. 22

CB 메카니즘용부속장치 CB Mechanism ➊ ➋ ➍ ➌ ➎ ➊ SHT 코일차단기를외부에서트립시키는제어장치로순시 (200ms 이상 ) 로전압을공급하였을때코일이동작합니다. ➋ Closing 코일차단기를외부에서투입하는제어장치로순시 (200ms 이상 ) 로전압을공급하였을때코일이동작합니다. ➌ MTD (Magnetic Tripping Device) 차단기를 OCR 에서트립시키는제어장치로단락이나과전류발생시동작합니다. * 트립시간은 OCR 의 t-setting 에서합니다. ➍ 보조스위치차단기의 ON/OFF 위치를원격으로감시하기위해사용하는접점입니다. ➎ 전동용모터외부전원을사용하여차단기의투입스프링을차지시킵니다. 동작전압범위 : 85%~110% Vn 23

부속장치 (Option) 트립경보접점 (CB-Trip Alarm Contact) 사고전류에의해서 OCR (Over Current Relay) 에의한차단기트립이발생했을경우차단기주커버에기계적인표시장치및내부보조스위치에의한전기적인제어신호를출력하여사고시차단기트립에대한정보를제공하는부속장치입니다. ( 본체내부에설치됨 ) AL2, 1a AL1, 1a 차단기가사고전류에의해서트립될때기계적인사고트립표시장치 (MRB, Manual Reset Button) 가전면주커버에서돌출되고, 전기적인제어신호를발생하는스위치 (AL) 는 Close 되어사고에의한차단기정보를외부로출력합니다. MRB 와 AL 은 OCR 에의한트립시에만동작하고 OFF 버튼과트립코일에의한 OFF 시에는동작하지않습니다. 트립후차단기를재투입할때에는기계적인사고표시장치 (MRB) 를눌러서차단기를리셋시켜야투입이가능합니다. 전기적인트립알람 (AL) 스위치는주문사양에따라서 1 개 (AL1, 1a) 혹은 2 개 (AL1, AL2, 1a) 가제공되며 Option 사양입니다. 트립경보접점과기계적인사고표시장치 (MRB) 는동시에구매해야합니다. 수동리셋버튼 (Manual Reset Button : MRB) OCR 에의해차단기트립동작한경우차단기동작을기구적으로방지한것을수동으로 RESET 하는기능입니다. 차단기가사고전류에의해서트립될때기계적인사고트립표시장치 (MRB, Manual Reset Button) 가전면주커버에서돌출되고, 전기적인제어신호를발생하는스위치 (AL) 는 Close 되어사고에의한차단기정보를외부로출력합니다. MRB 는일반적인차단기 OFF 동작으로는동작되지않고, OCR 에의한트립이발생되었을때만동작됩니다. 이때차단기를재투입하고자할때에는 MRB 를눌러서차단기를 Reset 시켜야투입동작이가능합니다 지락표시기, EFI (Earth Fault Indicator) EFI 는 RMU 본체나고객이원하는곳에설치가능합니다. 단상 AC 공급분할코어형센서 AC220~230V3Ph 에서자동리셋기능 3 상 24

동작순서도 CB 동작순서도 투입동작시작투입신호제어전원 "ON" 투입스프링자동차지시간 (5초) 투입동작완료트립신호차단동작시작차단동작완료 모터투입스프링차단스프링투입코일트립코일주접점 투입시간 개극시간 LBS 동작순서도 투입동작완료투입동작시작투입시모터동작시간 (8초) 개방시모터동작시간 (8 초 ) 개방동작시작개방동작완료 모터 투입 / 차단스프링 주접점 투입시간 개극시간 F-LBS 동작순서도 모터투입스프링차단스프링트립코일주접점 투입동작시작투입시모터동작시간 (8초) 투입동작완료개방신호 개방동작시작개방동작완료 투입시간 개극시간 25

외형도 1. 일체형 LBS Feeder 단독구성 RMU 4-18 32 779 635 75 1186 1222 B A-view Type A B LR 718 638 LLL 1030 950 LLLL 1362 1282 A A 725 752 2. 일체형 CB Feeder 구성 RMU 4-18 32 779 635 75 1400 1436 B A-view Type A B RC 718 638 LC 718 638 LCL 1030 950 LLCL 1362 1282 LCCL 1362 1282 A A 725 752 26

외형도 3. 일체형 Switch-Fuse Feeder 구성 RMU 4-18 32 779 635 75 1400 1437 B A-view Type A B RF 718 638 LF 718 638 LFL 1030 950 LLFL 1362 1282 LFFL 1362 1282 A A 725 752 4. 열반형 RMU 4-18 32 779 1437 1456 635 80 B A-view Type A B R 411 341 L 411 341 C 521 451 F 521 451 A A 724.3 752 27

형명체계 1. 일체형 LBS Feeder 단독구성 RMU LR B 24 6 0 0 0 형식 제어전원 정격전압 정격전류 ( 모선 ) 정격전류 (T-off) 정격주파수 제품형태 LR 수동 B 24kV 24 630A 6 N/A 0 60/50Hz 0 SKD S LLL AC 110V A1 17.5kV 17 CKD C LLLL AC 220V A2 12kV 12 완제품 0 DC 110V D1 DC 220V D2 2. 일체형 CB Feeder 구성 RMU RC B 24 6 6 6 0 형식 제어전원 정격전압 정격전류 ( 모선 ) 정격전류 (T-off) 정격주파수 제품형태 RC 수동 B 24kV 24 630A 6 630A 6 60Hz 6 SKD S LC AC 110V A1 17.5kV 17 50Hz 5 CKD C LCL AC 220V A2 12kV 12 60/50Hz 0 완제품 0 LLCL DC 110V D1 LCCL DC 220V D2 3. 일체형 Switch-Fuse Feeder 구성 RMU RF B 24 6 6 6 0 형식 제어전원 정격전압 정격전류 ( 모선 ) 정격전류 (T-off) 정격주파수 제품형태 RF 수동 B 24kV 24 630A 6 200A 2 60/50Hz 0 SKD S LF AC 110V A1 17.5kV 17 CKD C LFL AC 220V A2 12kV 12 완제품 0 LLFL DC 110V D1 LFFL DC 220V D2 4. 열반형 RMU R B 24 6 6 6 0 형식 제어전원 정격전압 정격전류 ( 모선 ) 정격전류 (T-off) 정격주파수 제품형태 R 수동 B 24kV 24 630A 6 630A 6 60Hz 6 SKD S L AC 110V A1 17.5kV 17 200A 2 50Hz 5 CKD C C AC 220V A2 12kV 12 60/50Hz 0 완제품 0 F DC 110V D1 DC 220V D2 28

품질보증 품질인증 Certified quality : STL (The Short-Circuit Testing Liaison, KERI), ISO 9001, ISO 14001 LSIS 는단위별기능조직을통합하여품질을확인하고표준준수를보장하고있습니다. 일상적인품질검사 Susol RMU 를생산하는과정에서아래와같은항목의일상적인테스트가실시됩니다. 압력검사 체결확인 수동및모터작동확인 절연검사 접촉저항검사 OCR 동작검사 29

Memo 30

Memo 31

안전에관한주의 제품을안전하게사용하기위해서 사용설명서 를읽고사용해주십시오. 본카탈로그에기재된제품은사용온도, 조건, 장소등이한정되어있으며, 정기점검이필요하므로제품구입처나당사에문의후정확하게사용해주십시오. 본카탈로그에기재된제품은예고없이단종이나사양변동이있을수있으므로구입시반드시확인바랍니다. 유지점검및보수시안전을위해임의적으로분해하거나수리하지마시고전기공사, 전기배선등전문기술을보유한사람에게연락하시기바랍니다. c 2015. 03 LSIS Co.,Ltd. All rights reserved. www.lsis.com 본사 : 경기도안양시동안구엘에스로 127 번지 ( 호계동 ) LS 타워 구입문의 저 고압차단기 TEL:(02)2034-4407, 08 FAX:(02)2034-4555 계량기 / 분전반 TEL:(02)2034-4217, 4473 FAX:(02)2034-4555 고압개폐기 TEL:(02)2034-4477 FAX:(02)2034-4555 계전 계측기기 TEL:(02)2034-4554 FAX:(02)2034-4555 원격검침시스템 TEL:(02)2034-4217 FAX:(02)2034-4555 부산영업 TEL:(051)310-6821~24 FAX:(051)310-6827 창원영업 TEL:(055)282-9812 FAX:(055)282-4352 울산영업 TEL:(052)261-1585 FAX:(052)922-2080 대구영업 TEL:(053)603-7711~15 FAX:(053)603-7777 광양영업 TEL:(070)4048-3230 FAX:(070)4048-3231 광주영업 TEL:(062)510-1811 FAX:(062)528-7684 대전영업 TEL:(042)820-4200~05 FAX:(042)820-4298 기술문의 고객센터 TEL:( 전국어디서나 )1544-2080 FAX:(041)550-8600 A/S문의 : 고객지원팀 서울 / 경기 TEL:( 전국어디서나 )1544-2080 FAX:(031)689-7021 부산 TEL:(051)310-6911~5 FAX:(051)310-6827 창원 TEL:(055)602-2080 FAX:(055)282-4352 울산 TEL:(052)261-1585 FAX:(052)922-2080 대구 TEL:(053)603-7721~3 FAX:(053)603-7777 광주 TEL:(062)510-1810~20 FAX:(062)528-7684 대전 TEL:(042)820-4206 FAX:(042)820-4298 교육 / 세미나문의 LS산전연수원 TEL:(043)268-2631~2 FAX:(042)268-2633~4 세미나 TEL:(02)2034-4533 Jisungp@lsis.biz LS 산전특약점 2016. 02 본제품의규격은품질개선을위하여예고없이변경될수있으므로제품구입시문의바랍니다. Susol Ring Main Unit (K) 2015. 03/ (03)2016. 02 Printed in Korea STAFF