방폭규정정의
1. 방폭규정정의 - IEC 방폭규정 (International Electrotechnical Commission) 규정정의 KS 규정 IEC 규정비고 1. 전기기기의방폭구조통칙 (Electrical apparatus for explosive gas atmospheres part 0. General requirements) KSC 0914-1995 IEC79-0 (1983) 2. 전기기기의耐壓방폭구조 (Ditto, part 1. Construction and verification test of flameproof enclosures of electrical apparatus) 3. 전기기기의內壓방폭구조 (Ditto, part 2. Electrical apparatus type of Protection P ) P ) KSC 0915-1995 IEC79-1 (1990) Ex d KSC 0916-1995 IEC79-2 (1983) Ex p 4. 전기기기의油入방폭구조 (Ditto part 6. oil-immersed apparatus) 5. 전기기기의안전증대방폭구조 (Ditto part 6. Increased safety e, Amendment NO1.) 6. 전기기기의본질안전방폭구조 (Ditto part 11. Intrinsic safety i ) KSC 0917-1995 IEC79-6 (1968) Ex o KSC 0918-1995 IEC79-7 (1990) Ex e KSC 0919-1995 IEC79-11 (1991) Ex ia
2. 방폭구조의설명 (IEC) 1. 내압방폭 ( Flameproof Type : Ex d ) 전폐구조로서, 용기내부에서폭발성가스가폭발했을때, 용기가그압력에견디고또한접합면이나개구부등을통해외부의폭발성가스에인화될우려가없도록한구조. 2. 압력방폭 ( Pressureized Type : Ex p ) 용기내부에질소등의불연성기체를압입하여, 내부압력을유지하여폭발성가스가침입할수없도록한구조. 3. 유입방폭 ( Oil Immersed Type : Ex o ) 전기기기의불꽃, 아크또는고온이발생하는부분을기름속에넣어기름면위에존재하는폭발성가스에인화될우려가없도록한구조. 4. 안정증방폭 ( Increased Safety Type : Ex e ) 정상운전중폭발성가스의점화원이되는불꽃또는고온이되어서는안되는부분에이것을방지하기위해, 기계적전기적으로안전도를증가한구조. 5 본질안전방폭 ( Intrinc Safety Type : Ex ia ) 5. 본질안전방폭 ( Intrinc Safety Type : Ex ia ) 정상시및사고시에발생하는전기불꽃의에너지가아주작고, 고온이되지않도록설계되어폭발성가스에점화가일어나지않는것이점화시험등에서확인된구조.
3. 방폭기기의분류 (IEC) 1] 방폭그룹에따른분류 1) GROUP Ⅰ : 탄광용의방폭전기기기 2) GROUP Ⅱ : 탄광이외의공장, 기타사업용의방폭전기기기 - 가스또는증기의분류에따라 A,B,C 가있슴 ( ⅡA > ⅡB > ⅡC ) A, B, C 분류에따른조건 가스또는증기의분류 가스또는증기의폭발성분위기중 최대안전틈새값 ( 耐壓 ) 최소점화전류비의값 ( 본질안전 ) 비고 ( 시험가스 ) A 0.9 mm 이상 0.8 초과프로판 B 0.5mm 초과 0.9mm 미만 0.45 이상 0.8 이하에칠렌 C 0.5mm 이하 0.45 미만 수소, 아세칠렌 비고 METHANE 의최소점화전류를기준으로구함
3. 방폭기기의분류 (IEC) 2] 폭발가스발화도에의한분류 온도등급 전기기기의최고표면온도값 ( ) 적용할 GAS 또는증기의발화온도값 ( ) 비고 T 1 450 이하 450 초과 T 2 300 이하 300 초과 T 3 200 이하 200 초과 T4 135 이하 135 초과 T 5 100 이하 100 초과 T 6 85 이하 85 초과
4. NEC (National Electric Code) NEC (National Electrical Code- 미국전기공사규정 ) 에따른위험장소의구분. 1. Class : 물성에따른분류 Class Ⅰ : 가연성가스나증기가존재하거나존재할수있는지역 (Group A,B,C,D) Class Ⅱ : 연소성먼지가존재하는지역 (Group E,F,G) Class Ⅲ : 인화성섬유또는부유물이존재하는지역. 2. 방폭그룹에따른분류 Group A : 대기중에아세틸렌포함. Group B : 대기중에수소가스또는증기포함. Group C : 대기중에에틸에테르증기, 에틸렌, 시크로프로판포함. Group D : 대기중에가솔린, 헥산, 나프타, 벤젠, 프로판, 알코올, 벤졸, 락커, 솔벤트증기, 천연가스포함. Group E : 대기중에마그네슘또는공업용합금등이포함되거나, 또는유사한다른위험한금속먼지를포함. Group F : 대기중에카본블랙콜또는코크먼지포함. Group G : 대기중에밀가루, 전분, 곡물등의먼지포함. 3. 위험장소에따른분류 Division 1 : 통상적인상태에서가연성의가스나증기가존재하는곳으로발화성이집중된장소. 또한누설과작동들때문에자주가스와증기가존재할수있는곳. Division 2 : 사고나비정상적인작동으로인하여가연성의액체나가스등이존재하는곳.
5. 국가별위험장소에따른비교. 국가 지속적인폭발분위기 통상상태에서간접적인폭발분위기 이상상태에서폭발분위기 한국 0 종장소 1 종장소 2 종장소 일본 0 종장소 1 종장소 2 종장소 IEC Zone 0 Zone 1 Zone 2 독일 Zone 0 Zone 1 Zone 2 영국 Division 0 Division 1 Division 2 미국 (NEC) Division 1 Division 2
6. 그룹에따른방폭등급의비교 IEC NEC Group IIC : acetylene Group IIC : hydrogen Group IIB : ethylene Group IIA : propane 더쉽게발화됨 Class I, Group A : acetylene Class I, Group B : hydrogen Class I, Group C : ethylene Class I, Group D : propane 더쉽게발화됨 Dusts Under Consideration Class II, Group E : metal dust Class II, Group F : carbon dust Class II, Group G : flour, starch, grain Mining i Industry Group I : methane (firedamp) Class III : fibers and flyings Mining Industry Unclassified : methane (firedamp)
7. 내압및본질안전방폭의사용장소적용 구분 IEC NEC Eex d ( 내압방폭 ) Zone 1 Zone 2 Class Ⅰ & Ⅱ, Div.1 Class Ⅰ & Ⅱ, Div.2 Eex ia ( 본질안전방폭 ) Zone 0 Zone 1 Zone 2 Class Ⅰ & Ⅱ, Div.1 Class Ⅰ & Ⅱ, Div.1 Class Ⅰ & Ⅱ, Div.2
8. NEMA 등급 NEMA (National Electrical Manufacturers Association) 등급 NEMA 의등급은다음에서보는 NEMA1~NEMA13 NEMA13 까지있으며,NEMA1~6, NEMA11~13 13 은안전지대에적용할수있는등급이며, NEMA7~10은위험지역에적용되는등급이다. NEMA8은기름속에서사용하여도자연발화를막을수있는등급을말하며, NEMA9는발화하기쉬운물질속에서의불꽃에도견디어낼수있는등급을말한다. 1 NEMA 1 방폭등급의첫번째로실내에서사용되는것으로서비스가잘되지않으며, 현재존재하지않는등급이다. 2 NEMA 2 실내에서사용할수있는첫번째등급으로제한된양의낙수와오물이나먼지에견디어줄수있는등급이다. 3 NEMA 3 실외에서사용되는첫번째등급으로흩날리는먼지, 비, 진눈개비등의조건하에사용할수있는등급으로내부동결이나응축등의조건에서는사용할수없다. 4NEMA 4 실내외에서사용되는등급으로흩날리는먼지, 비, 물등의조건하에사용할수있고내부동결이나응축등의조건에서는사용이불가하다. 5 NEMA 5 실내에서사용되는등급으로먼지와오물, 부식성이없는유체등에사용할수있고내부응축에서는사용할수없다. 6NEMA 6 실내외에서사용되는등급으로제한된깊이의물속에서사용이가능하고얼음등의충격에도무관하나내부동결이나응축에서사용이불가하다.
7 NEMA 7 불꽃이발생하지않는지역에서가스등의위험출하에도사용가능한등급이다. 8 NEMA 8 기름속에서사용이가능하고불꽃이없는가스에서도사용가능한등급으로실외에서의사용조건은 NEMA4 와같다. 9 NEMA 9 유입되는먼지하의조건에서사용이가능하다. 10NEMA 10 낙뢰등에견디어줄수있는등급이다. 11NEMA 11 실내에서사용되는등급이며부식성유체나가스등의조건하에서사용이가능하다. 또한부식성증기와기름속에서의사용도가능한등급이다. 12NEMA 12 실내에서사용되는조건으로먼지와오물그리고부식성이없는유체하에서사용가능한등급이다. 13 NEMA 13 13 NEMA 13 실내에서사용되는조건으로먼지와뿌려지는물, 오일그리고부식성이없는냉각제등에서사용할수있는등급이다.
9. IP (International Protection) 등급 IP 등급 ( 용기의보호등급 ) 은 IP 과같이두자리숫자로표시되며, 그숫자에따른보호등급은다음과같다. 첫째숫자 인체및고형이물질에관한보호등급 둘째숫자 물의침입에대한보호등급 0 1 2 3 -(no protection) 손에의한접촉혹은큰물체의접근에대한보호손가락혹은중간크기의물체의접근에대한보호 2.5mm 물체의접촉에대한보호 0 1 2 3 -(No special protection) 수직으로떨어지는물방울에대한보호 15 의각도까지떨어지는물방울에대한보호 60 의각도까지분무된물에대한보호 4 1mm 의작은물체의접촉에대한보호 4 어느방향에서도분무되는물에대한보호 5 물리적인접촉과먼지의침투에대한보호 6 물리적인접촉과먼지침투에대한전체적인보호 5 6 7 8 물분사 (Water Jet) 에대한보호 강한물분사 (Powerful Water Jet) 에대한보호압력과시간의지정된조건하에서의물속에서의보호 (Temporary Immersion) 7 보다심한조건하에서계속적인물속에서의보호 (Continuous Immersion)
10. 주로사용하는 Model 의적용 Solenoid Valve Limit Switch Maker Exd IIB ASCO JE3 Series COSHA Exd IIB+H2 or KGS JBEF & JE3 Series COSHA or KGS Exd IIC COSHA or KGS Exia IIC COSHA or KGS NF Series WBIS Samson -- -- -- 3963-1 Kaneko Yamatake AE12PU, DE12PU 1LX 5001/3, VCX5001/3 Series -- -- -- -- 1LX 5701 Series(Ex de ) -- HKC APL-420 -- -- -- APL-420N Westlock 2200,2300 Series X -- -- 2645 & X 2147 & X Avid Model XA X -- -- -- -- Model ZR X Yamatake AVP 300 Samson 3780-1 E/P Positioner SMC IP8100 -- -- -- -- -- -- AVID -- -- -- -- -- -- Smartcal ( ib ) X Fisher -- -- DVC 6000 Series -- --