Air Conditioning Technical Data ARXS-L
Outdoor Unit ARXS-L TABLE OF CONTENTS ARXS-L 1 Features............................................................. 2 2 Specifications....................................................... 3 Capacity and Power input............................................ 3 Capacity and Power input............................................ 3 Technical Specifications............................................. 4 Electrical Specifications.............................................. 6 3 Electrical data....................................................... 7 4 Capacity tables..................................................... 9 Cooling/Heating Capacity Tables.................................... 9 5 Dimensional drawings............................................ 12 6 Centre of gravity................................................... 14 7 Piping diagrams................................................... 16 8 Wiring diagrams................................................... 18 Wiring Diagrams - Single Phase.................................... 18 9 Sound data......................................................... 19 Sound Pressure Spectrum.......................................... 19 Sound Pressure Spectrum - Cooling................................ 20 Sound Pressure Spectrum - Heating................................ 21 10 Operation range................................................... 22 Split - Sky Air ARXS-L 1
t y i k n u - r o L t o - id lt pu 1 Features Outdoor Unit ARXS-L t S U S X R OS A SEER / SCOP up to A++ Outdoor unit silent operation: "silent" button on the remote control lowers the operation sound of the outdoor unit by 3dBA to ensure a quiet environment for the neighbourhood. Outdoor units for pair application 1 The use of inverter type outdoor units results in an air conditioning system with a high energy efficiency and very low sound level Daikin outdoor units are neat, sturdy and can easily be mounted on a roof or terrace or simply placed against an outside wall Outdoor units are fitted with a swing compressor, renowned for its low noise and high energy efficiency Energy saving during standby mode Auto coolingheating changeover Outdoor unit silent operation 2 Split - Sky Air ARXS-L
2 Specifications Outdoor Unit ARXS-L 2-1 Capacity and Power input ATXS50K/ARXS50L Indoor unit ATXS50K Outdoor unit ARXS50L Cooling capacity Min. kw 1.7 Btu/h 5,800 kcal/h 1,460 Nom. kw 5.00 (1) Btu/h 17,100 (1) kcal/h 4,300 (1) Max. kw 5.3 Btu/h 18,100 kcal/h 4,560 Heating capacity Min. kw 1.7 Btu/h 5,800 kcal/h 1,460 Nom. kw 5.80 (1) Btu/h 19,800 (1) kcal/h 4,990 (1) Max. kw 6.5 Btu/h 22,200 kcal/h 5,590 Power input Cooling Min. kw 0.350 Nom. kw 1.587 (1) Max. kw 1.810 Heating Min. kw 0.300 Nom. kw 1.450 (1) Max. kw 2.000 Seasonal efficiency Cooling Pdesign kw 5.00 (according to SEER 6.46 EN14825) Annual energy kwh 271 consumption Heating (Average Pdesign kw 4.60 climate) SCOP/A 4.00 Annual energy kwh 1,608 consumption Piping connections Liquid OD mm 6.35 Gas OD mm 12.7 Drain OD mm 18 Heat insulation Both liquid and gas pipes Current Nominal running Cooling A 7.43 (2) / 7.09 (3) / 6.75 (4) current (RLA) - 50Hz Heating A 6.8 (2) / 6.5 (3) / 6.2 (4) Nominal efficiency EER 3.15 (5) COP 4.00 (5) Annual energy consumption kwh 794 3 2 Notes (1) Nominal efficiency: cooling at 35 /27 nominal load, heating at 7 /20 nominal load (2) 220V (3) 230V (4) 240V (5) EER/COP according to Eurovent 2012, for use outside EU only 2-2 Capacity and Power input ADEQ50C/ARXS50L ADEQ60C/ARXS60L ADEQ71C/ARXS71L Indoor unit ADEQ50C ADEQ60C ADEQ71C Outdoor unit ARXS50L ARXS60L ARXS71L Cooling capacity Nom. kw 5.00 (1) 5.70 (1) 6.80 (1) Heating capacity Nom. kw 5.50 (1) 7.00 (1) 7.50 (1) Split - Sky Air ARXS-L 3
2 Specifications Outdoor Unit ARXS-L 2 2-2 Capacity and Power input ADEQ50C/ARXS50L ADEQ60C/ARXS60L ADEQ71C/ARXS71L Power input Cooling Nom. kw 1.56 1.70 2.55 Heating Nom. kw 1.48 1.94 2.16 Seasonal efficiency Cooling Pdesign kw 5.00 5.70 6.80 (according to SEER 5.60 5.70 5.30 EN14825) Annual energy kwh 313 350 449 consumption Heating (Average Pdesign kw 4.40 4.60 6.00 climate) SCOP/A 4.00 3.80 Annual energy consumption kwh 1,540 1,610 2,210 Current - 50Hz Maximum running current A 18.0 19.5 Current Nominal running current (RLA) - 50Hz Cooling A 5.3 6.1 11.0 Eurovent Sound power level outdoor Cooling Nom. dba 62 65 Sound power level indoor Cooling Nom. dba 60 56 Notes (1) Nominal efficiency: cooling at 35 /27 nominal load, heating at 7 /20 nominal load EER/COP according to Eurovent 2012, for use outside EU only PED: assembly = category l : excluded from scope of PED due to article 1, item 3.6 of 97/23/EC Minimum Ssc (=Short-circuit power) value: Equipment complying with EN 61000-3-2 See separate drawing for electrical data Contains fluorinated greenhouse gases 2-3 Technical Specifications ARXS50L ARXS60L ARXS71L Capacity control Method Inverter controlled Casing Colour Ivory white Dimensions Unit Height mm 735 Width mm 825 Depth mm 300 Packed unit Height mm 797 Width mm 992 Depth mm 390 Weight Unit kg 47 Packed unit kg 52 Packing Weight kg 5 - Heat exchanger Length mm 845 Rows Quantity 2 Fin pitch mm 1.8 Stages Quantity 32 Tube type ø8 Hi-XD ø8 Hi-XSL Tube material - Copper Tube diameter mm - 8 Fin Type Precoat Fin Waffle fin (PE) Compressor Quantity - 1 Model 2YC36BXD#C Oil Amount cm³ - 650 Type Hermetically sealed swing compressor Output W 1,100 1,100.0 Oil Type - Daphne FVC50K 4 Split - Sky Air ARXS-L
2 Specifications Outdoor Unit ARXS-L 2-3 Technical Specifications ARXS50L ARXS60L ARXS71L Fan Type Propeller fan Propeller Discharge direction - Horizontal Quantity - 1 Air flow rate Cooling Nom. m³/min - 50.9 56.5 High cfm 1,797 - m³/min 50.9 - Super cfm 1,727 - low m³/min 48.9 - Heating High m³/min 45.0 - cfm 1,589 - Nom. m³/min - 46.3 Super cfm 1,522 - low m³/min 43.1 - Fan motor Quantity - 1 Model KFD-380-50-8D Insulation grade - Class "E" Poles - 8 Output W 53 Speed Cooling High rpm 780 - Super rpm 670 - low Heating High rpm 720 - Super low rpm 670 - Sound power level Cooling dba 62 65 Heating dba 62 65 Sound pressure level Cooling High dba 48 - Nom. dba - 49 52 Silent operation dba 44 - Heating High dba 48 - Nom. dba - 49 52 Silent operation dba 45 - Operation range Cooling Ambien Min. CDB 10-10 t Max. CDB 46 Heating Ambien Min. CWB -15 t Max. CWB 18 Refrigerant Type R-410A Charge kg 1.7 1.50 1.70 TCO 2 eq 3.5 - Control - Expansion valve (electronic type) GWP 2,087.5 Piping connections Liquid Quantity - 1 Type - Flare connection OD mm - 6,35 9,52 Gas Quantity - 1 Type - Flare connection OD mm - 12.7 15.9 Drain Type - Hole OD mm - 18 ID mm - Piping length OU - IU Max. m 30 System Chargel ess m 10 Additional refrigerant charge kg/m 0.02 (for piping length exceeding 10m) Level difference IU - OU Max. m 20 Refrigerant oil Charged volume l 0.650 - Type FVC50K - Defrost method - Reversed cycle Defrost control - Sensor for outdoor heat exchanger temperature 3 2 Split - Sky Air ARXS-L 5
2 Specifications Outdoor Unit ARXS-L Standard Accessories : Drain plug; Quantity : 1; Standard Accessories : Installation manual; Quantity : 1; Standard Accessories : Refrigerant charge label; Quantity : 1; Standard Accessories : Multilingual fluorinated greenhouse gases labels; Quantity : 1; 2 2-4 Electrical Specifications ARXS50L ARXS60L ARXS71L Power supply Name V1 Phase 1~ Frequency Hz 50 Voltage V 220-240 220-230-240 Voltage range Min. % - 10 Max. % - 10 Current - 50Hz Maximum fuse amps (MFA) A - Current Nominal running Cooling A 6.48 (1) / 6.18 (2) / 5.89 (3) 6.1 11.0 current (RLA) Heating A 6.65 (1) / 6.36 (2) / 6.06 (3) - Starting current Cooling A 6.8 9.4 - Heating A 6.8 - Maximum running Cooling A - 18.0 19.5 current Heating A - 18.0 19.5 Current - 60Hz Maximum fuse amps (MFA) A - Wiring connections For power supply Quantity - 3 Remark 3 for power supply, 4 for interunit - wiring (including earth wiring) For connection with Quantity - 4 indoor Remark - 4 wires (earth wire included) Notes (1) 220V (2) 230V (3) 240V When connected with multi-system outdoor unit, refer to the specifications of the multi outdoor unit to be connected. Contains fluorinated greenhouse gases 6 Split - Sky Air ARXS-L
3 Electrical data 3-1 Electrical Data ARXS50L Outdoor Unit ARXS-L 3 Unitcombinationrestrictions Powersupply COMP OFM IFM Indoorunit Outdoorunit ATXS50K3V1B ARXS50L2V1B 50 Hz Voltage Voltagerange MCA MFA RHz RLA kw FLA kw FLA 220 Max.50Hz264V 6,3 230 15,5 20 65 6,0 240 Min.50Hz198V 5,7 0,053 0,27 0,023 0,15 3 Symbols MCA: MinimumCircuitAmpere(A) MFA: MaximumFuseAmpere(A) RLA: Ratedloadamps[A] OFM: Outdoorfanmotor IFM: Indoorfanmotor FLA: FullLoadAmpere(A) kw: Fanmotorratedoutput[kW] RHz: Ratedoperatingfrequency[Hz] Notes 1. TheRLAisbasedonthefollowingconditions. Indoortemperature27 CDB/19 CWB Outdoortemperature35 CDB 2. SelectthewiresizeaccordingtotheMCA. 3. Themaximumallowablevoltagethatisunbalancedbetweenphasesis2%. 4. Useacircuitbreakerinsteadofafuse. 3D096942 ADEQ35-71C Split - Sky Air ARXS-L 7
3 Electrical data 3-1 Electrical Data Outdoor Unit ARXS-L 3 ADEQ71C_ARXS71L 8 Split - Sky Air ARXS-L
Outdoor Unit ARXS-L 4 Capacity tables 4-1 Cooling/Heating Capacity Tables ATXS50K3V1B+ARXS50L2V1B 3 Cooling50Hz220240V 4 AFR 11,9 BF 0,13 Indoor Outdoortemperature[ CDB] EWB EDB 20,0 25,0 30,0 32,0 35,0 40,0 C C TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI TC SHC PI 14,0 20,0 3,41 2,72 1,11 3,41 2,72 1,27 3,41 2,72 1,43 3,41 2,72 1,50 3,41 2,72 1,57 3,41 2,72 1,69 16,0 22,0 4,56 3,14 1,18 4,56 3,14 1,33 4,56 3,14 1,45 4,56 3,14 1,51 4,56 3,14 1,58 4,42 3,07 1,69 18,0 25,0 5,58 3,66 1,23 5,35 3,55 1,35 5,12 3,45 1,47 5,02 3,40 1,51 4,88 3,34 1,59 4,65 3,24 1,70 19,0 27,0 5,70 3,83 1,24 5,47 3,72 1,35 5,23 3,62 1,48 5,14 3,58 1,52 5,00 3,52 1,59 4,77 3,42 1,70 22,0 30,0 6,04 3,68 1,25 5,81 3,59 1,36 5,58 3,50 1,49 5,49 3,46 1,53 5,35 3,40 1,60 5,11 3,32 1,71 24,0 32,0 6,27 3,57 1,25 6,04 3,49 1,38 5,81 3,40 1,49 5,72 3,37 1,53 5,58 3,32 1,61 5,34 3,24 1,73 Heating50Hz220240V AFR 13,3 Indoor Outdoortemperature[ CWB] EDB 15,0 10,0 5,0 0,0 6,0 10,0 C TC PI TC PI TC PI TC PI TC PI TC PI 15,0 2,76 0,93 3,32 0,98 3,88 1,03 5,21 1,35 6,00 1,42 6,52 1,47 20,0 2,59 0,96 3,15 1,01 3,71 1,05 5,01 1,38 5,80 1,45 6,32 1,50 22,0 2,52 0,97 3,08 1,02 3,64 1,07 4,93 1,39 5,72 1,46 6,24 1,51 24,0 2,46 0,98 3,01 1,03 3,57 1,08 4,85 1,40 5,64 1,48 6,16 1,52 25,0 2,42 0,99 2,98 1,03 3,54 1,08 4,81 1,41 5,60 1,48 6,12 1,53 27,0 2,35 1,00 2,91 1,04 3,47 1,09 4,73 1,42 5,52 1,50 6,04 1,54 Symbols AFR: BF: EWB: EDB: TC: SHC: PI: Airflowrate[m³/min] Bypassfactor Enteringwetbulbtemperature( CWB) Enteringdrybulbtemperature( CDB) Totalcapacity[kW] Sensibleheatcapacity[kW] Powerinput[kW] Notes 1) Theratingsshownarenetcapacitieswhichincludeadeductionforindoorfanmotorheat. 2) Theboldcellsindicatethestandardconditions. 3) Thetotalcapacity,powerinputandsensibleheatcapacitymustbecalculatedbyinterpolation,usingthefiguresinthetable(figuresnotinthetablemaynot beusedinthecalculation). 4) Incasethesensibleheatcapacityisnotmentionedinthetable,pleasecalculateitusinganapproximationbetweentwovaluesindirectproportion. 5) Thecapacitiesarebasedonthefollowingconditions: Correspondingrefrigerantpipinglength:5m Leveldifference:0m 6) Theairflowrateandbypassfactorarementionedinthetable. 3D096948 Split - Sky Air ARXS-L 9
Outdoor Unit ARXS-L 4 Capacity tables 4-1 Cooling/Heating Capacity Tables ADEQ50C + ARXS50L2 4 ADEQ60C + ARXS60L2 10 Split - Sky Air ARXS-L
Outdoor Unit ARXS-L 4 Capacity tables 4-1 Cooling/Heating Capacity Tables ADEQ71C + ARXS71L2 3 4 Split - Sky Air ARXS-L 11
Outdoor Unit ARXS-L 5 Dimensional drawings 5-1 Dimensional Drawings 5 ARXS60L2 3D107437 12 Split - Sky Air ARXS-L
Outdoor Unit ARXS-L 5 Dimensional drawings 5-1 Dimensional Drawings ARXS71L2 3 5 3D107436 Split - Sky Air ARXS-L 13
6 Centre of gravity 6-1 Centre of Gravity Outdoor Unit ARXS-L 6 14 Split - Sky Air ARXS-L
6 Centre of gravity 6-1 Centre of Gravity Outdoor Unit ARXS-L 3 ARXS60-71L2 6 4D107435 Split - Sky Air ARXS-L 15
7 Piping diagrams 7-1 Piping Diagrams Outdoor Unit ARXS-L 7 ARXS60L2 3D107502 16 Split - Sky Air ARXS-L
7 Piping diagrams 7-1 Piping Diagrams Outdoor Unit ARXS-L ARXS71L2 3 7 3D107501 Split - Sky Air ARXS-L 17
Outdoor Unit ARXS-L 8 Wiring diagrams 8-1 Wiring Diagrams - Single Phase ARXS60-70L 8 18 Split - Sky Air ARXS-L
Outdoor Unit ARXS-L 9 Sound data 9-1 Sound Pressure Spectrum ARXS60L2 3 90 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10 NR0 NR90 NR85 NR80 NR75 NR70 NR65 NR60 NR55 NR50 NR45 NR40 NR35 NR30 NR25 NR5 NR10 NR15 NR20 63 125 250 500 1000 2000 4000 8000 dba 90 80 70 60 50 40 30 20 10 90 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10 NR0 NR90 NR85 NR80 NR75 NR70 NR65 NR60 NR55 NR50 NR45 NR40 NR35 NR30 NR25 NR5 NR10 NR15 NR20 63 125 250 500 1000 2000 4000 8000 dba 90 80 70 60 50 40 30 20 10 9 ARXS71L2 90 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10 NR0 NR5 NR10 NR15 NR20 NR90 NR85 NR80 NR75 NR70 NR65 NR60 NR55 NR50 NR45 NR40 NR35 NR30 NR25 63 125 250 500 1000 2000 4000 8000 dba 90 80 70 60 50 40 30 20 10 90 85 80 75 70 65 60 55 50 45 40 35 30 25 20 15 10 NR90 NR85 NR80 NR75 NR70 NR65 NR60 NR55 NR50 NR45 NR40 NR35 NR30 NR0 NR25 NR5 NR10 NR15 NR20 63 125 250 500 1000 2000 4000 8000 dba 90 80 70 60 50 40 30 20 10 Split - Sky Air ARXS-L 19
Outdoor Unit ARXS-L 9 Sound data 9-2 Sound Pressure Spectrum - Cooling 9 20 Split - Sky Air ARXS-L
Outdoor Unit ARXS-L 9 Sound data 9-3 Sound Pressure Spectrum - Heating 3 9 Split - Sky Air ARXS-L 21
10 Operation range 10-1 Operation Range Outdoor Unit ARXS-L ARXS60-71L2 10 3D100846B 22 Split - Sky Air ARXS-L
Daikin Europe N.V. Naamloze Vennootschap - Zandvoordestraat 300, B-8400 Oostende - Belgium - www.daikin.eu - BE 0412 120 336 - RPR Oostende EEDEN17 01/17 Daikin Europe N.V. participates in the Eurovent Certification programme for Liquid Chilling Packages (LCP), Air handling units (AHU), Fan coil units (FCU) and variable refrigerant flow systems (VRF) Check ongoing validity of certificate online: www.eurovent-certification.com or using: www.certiflash.com The present leaflet is drawn up by way of information only and does not constitute an offer binding upon Daikin Europe N.V.. Daikin Europe N.V. has compiled the content of this leaflet to the best of its knowledge. No express or implied warranty is given for the completeness, accuracy, reliability or fitness for particular purpose of its content and the products and services presented therein. Specifications are subject to change without prior notice. Daikin Europe N.V. explicitly rejects any liability for any direct or indirect damage, in the broadest sense, arising from or related to the use and/or interpretation of this leaflet. All content is copyrighted by Daikin Europe N.V.